InteliDrive Lite, SW version 1.9  
ID-FLX-Lite-1.9r1 Reference Guide.pdf, ©ComAp – August 2015   
7.5.4  Request 1      [-] 
Regulator requested value. 
Step:     1  
Range:    -10000 - +10000  
Default:   0 
7.5.5  Request 2      [-] 
Regulator requested value when LBI Request2 is active. 
Step:     1  
Range:    -10000 - +10000  
Default:   0 
7.5.6  Reg Gain      [%] 
This setpoint is giving regulator gain factor. See Hint below. 
Step:     0.1%  
Range:   -200.0 - +200.0% 
Default:   10% 
7.5.7  Reg Integral    [%] 
This setpoint is giving regulator integration factor. See Hint below. 
Step:     0.1  
Range:    0.0% - +100.0%  
Default:   10% 
HINT 
InteliDrive Lite controllers include PI loop for speed or analog output regulation. The requested value 
is  given  by  setpoints  Request  1,  2.  This  loop  is  working  like  Proportional-Integral  regulation  with 
setpoints Reg Gain and Reg Integral for each part and these parts affect each other.  
The controller output is given by: 
Reg Gain * e(t) + Reg Integral * ʃ e(t) dt,  
where e(t) is deviation of actual value e(t) = Request 1, 2 – Measured value.