InteliDrive Lite, SW version 1.9  
ID-FLX-Lite-1.9r1 Reference Guide.pdf, ©ComAp – August 2015   
CAUTION! 
More information about ECU list packages, values, configuration and wiring recommendations can be 
found in Comap Electronic Engines Support manual. 
The  InteliDrive  Lite  controller  always  sends  either  speed  request = 0 %  or  the  IDLE  command  via 
J1939 in controller Idle state.  In the MAN mode the Idle operation can be controlled by Nominal/Idle 
binary input. 
11.5  Choosing the ECU to configure 
According to the model of ECU, choose and configure the right ECU option. The configuration can be 
made in LiteEdit, the window Modify, icon ECU.  
 
 
HINT 
If  the  connected  engine  is  Cummins  communicating via  RS232,  it  is necessary  to  set the  setpoint 
Basic settings: COM1 mode (or COM2 mode if IL-NT-RS232-485) = ECULINK. 
Loss of  communication causes shutdown of the running engine.  On the contrary, the  ECU can  be 
switched  off  at  quiescent  engine  that  means  not-communicating  ECU  is  in  that  moment  normal 
situation. All values from ECU shall show ####, but no alarm is displayed. The output ECU CommOK 
follows the real situation that means it is not active anytime when the ECU does not communicate. 
The  output  ECU  PwrRelay  closes  at  the  beginning  of  prestart  and  opens  if  the  engine  shall  be 
stopped. 
The engine is started via standard contact output or via CAN bus.