InteliDrive Lite, SW version 1.9  
ID-FLX-Lite-1.9r1 Reference Guide.pdf, ©ComAp – August 2015   
7.4.27  100%ofSpeedReq       [RPM] 
Limit for Speed Request transformation from RPM to % range for ECU engines using % format. 
Step:     1RPM 
Range:    0 - 4000RPM 
Default:   2000RPM 
7.4.28  Conveyor horn                          [s] 
Horn time before the conveyor output starts.  
Step:     1s 
Range:    0 - 600s 
Default:   7s 
7.4.29  Running timer       [min] 
Automatic engine stop in MAN mode or delayed engine stop in AUT mode. Start engine in MAN mode 
by START button. Engine stops itself after Running Timer is over. Engine stays running when Running 
Timer = 0 
Step:     1min 
Range:    0 - 1000min 
Default:   0min 
7.4.30  FuelTankVolume      [L] 
This setpoint is describing volume of fuel tank for counting fuel consumption depending on Fuel level 
drop. 
Step:     1L 
Range:    0 – 10000L 
Default:   200L 
7.4.31  MaxFuelDrop        [%/h]    
This is setting protection against the fuel leakage or theft.    
Function monitors  the  AIN3 Fuel  level  value in  percentage  scale  without  decimals.  The alarm  and 
history  record  “Wrn  FuelTheft”  is  activated  when  Fuel  level  change  is  faster  than  setpoint  limit.  
Function is switched off when Max Fuel Drop = 0 %/h. 
The drop out limit on stopped engine is 5% to avoid unwanted Alarm activation due to AIN3: Fuel level 
fluctuations. 
Active alarm "Wrn FuelTheft" can be sent via SMS and displayed by WebSupervisor (if used).   
Step:    1 
Range:   0 - 50% 
Default:   25% 
HINT 
Set 0 to disable Fuel Theft Protection function into MaxFuelDrop setpoint.