InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf, ©ComAp – August 2015
7.8.3 Time [HH:MM:SS]
Actual time.
7.8.4 Date [DD:MM:YYYY]
Actual date.
7.8.5 Timer1Function [NoFunc, AutoRun, AutoRegCMP, AutoBatt,
AutoStop]
No Func: Operates just corresponding LBO Timer1 according the Timer1 setting, see Timer1
repeat, Time1 ON time, Timer1Duration. Function operates in all OFF-MAN-AUT
modes. Default state.
AutoRun: Engine automatically starts and stops in AUT mode (similar to LBI Rem start/stop, the
same record in the history) according the Timer1 setting.
AutoRegCMP: Start and stop engine in AUT mode according to the LBO Speed switch - see
Regulator: Reg CMP setpoints. The comparator function (output) works opposite
when Regulator: Reg CMP On < Reg CMP Off. The Date/Time: Timer1 repeat,
Timer1 ON time, Timer1Duration settings are not important in this case.
AutoBatt: Engine starts when actual Battery voltage < Engine protect: Batt undervolt + Batt volt
del and stays running for Date/Time: Timer1 Duration. Function operates in AUT
mode.
AutoStop: Engine is switched from AUT to MAN and stopped or stopped from MAN mode (like by
STOP button) when engine runs longer then Date/Time: Timer1Duration on actual
RPM less or equal Engine params: Idle speed + 5% (fix limit). Function is not active
during engine start.
7.8.6 Timer1repeat [NONE, MONDAY, TUESDAY, WEDNESDAY,
THURSDAY, WEDNESDAY, FRIDAY,
SATURDAY, SUNDAY, MON-FRI, MON-SAT,
MON-SUN, SAT-SUN]
This setpoint defines Timer1 activation. Binary output Timer1 is internally linked with Rem Start/Stop
binary input. Refer to binary inputs for details.
NONE: Timer function is disabled. Defualt state.
MONDAY, TUESDAY, WEDNESDAY, THURSDAY, WEDNESDAY, FRIDAY, SATURDAY, SUNDAY:
Timer is activated on daily basis.
MON-FRI, MON-SAT, SAT-SUN:
Timer is activated on selected day interval.
7.8.7 Timer1 ON time [HH:MM:SS]
Display day time when Timer 1 output is activated.
7.8.8 Timer1Duration [min]
Adjusts duration of Timer 1 output.