InteliDrive Lite, SW version 1.9  
ID-FLX-Lite-1.9r1 Reference Guide.pdf, ©ComAp – August 2015   
9.3.8  Remote AUT 
If the input is active, AUT mode is forced to the controller independently on the position of the MODE 
selector. If another of remote inputs is active, then the Remote AUT input has the lowest priority. 
9.3.9  RemControlLock 
If the input is active, setpoints writing or command sending from the external terminal is disabled.  
9.3.10  Emerg. manual 
If the input is activated the controller behaves like when switched to OFF mode and opens all binary 
outputs. There is one exception – Stop solenoid doesn’t activate on this transition.  
Detection of running engine and subsequent alarm message "Sd Stop fail" is blocked. 
The controller shows “Emerg Man” state and the engine can not be started.  
After the input is open again, the controller recovers to previous state and behaves according to the 
actual situation. 
Function is active in any controller mode. 
9.3.11  StartButton 
Binary input has the same function as  Start button on the InteliDrive Lite front panel. It is active in 
MAN mode only.  
9.3.12  StopButton 
Binary input has the same function as  Stop button on the InteliDrive Lite front panel. It is active in 
MAN mode only.  
9.3.13  FaultResButton 
Binary input has the same function as Fault reset button on the InteliDrive Lite front panel.  
9.3.14  HornResButton 
Binary input has the same function as Horn reset button on the InteliDrive Lite front panel.  
9.3.15  Nominal/Idle 
Input works in MAN mode only switching between  running states Nominal/Idle.  Active Nominal/Idle 
input activates binary  output  Idle/Nominal and  sends  Speed request = Engine  params:  Idle speed 
and/or active (binary) IDLE command to the ECU (e.g. to Volvo EMS). 
 
Engine params: Idle speed 
Engine params: Idle speed 
 
Engine params: ECU SpeedAdj 
… anything within  
Engine params: MinSpeedLim 
Engine params: MaxSpeedLim