InteliDrive Lite, SW version 1.9  
ID-FLX-Lite-1.9r1 Reference Guide.pdf, ©ComAp – August 2015   
7.2.3  RPMbyWterminal    [-] 
The constant of this setpoint multiplies the speed value obtained from the controller input RPM.  
Step:     0.01 
Range:    0.5 - 2 
 
HINT 
The default value is and must be 1, when the classical pick-up speed sensor is used to measure the 
engine speed.  
The setpoint is usefull when the engine does not have the speed sensor and the speed is measured 
by  the  W  terminal  of  the  charging  alternator.  The  setpoint  allows  tuning  the  ratio  between  the 
frequency  and  the  RPM  value  which  can  not  to  correspond  to  the  entire  values  of  teeth  numbers 
(because of the different non-integral ratio of the engine and alternator pulleys).  
7.2.4  Nominal RPM      [RPM] 
Nominal engine speed, base for overspeed protection and scale on RPM gauges. 
Step:     1RPM 
Range:    100 - 4000RPM 
7.2.5  GearTeethBI3      [-] 
The second RPM (RPM-BI3 value) can be measured in limited frequency range 1 to 50Hz on Binary 
input  3.  The  RPM-BI3  value  indicates  RPM  calculated  from  BI3  frequency  and  Basic  settings: 
GearTeeth3 setpoint.  
The RPM-BI3 value =0 below 1Hz and =### over 50Hz.   
Configure BI Type = Not used and change the name according the function for RPM-BI3 measuring. 
HINT 
The  RPM-BI3  measuring  is  switched off  when  Basic  setting:  GearTeethBI3  =  0.  In  this  case  BI3 
operates as standard Binary input. 
Step:    1 
Range:   0 - 10 
7.2.6  RPM source       [Pickup, AIO-AIN1, AIO-AIN2, AIO-AIN3, AIO-AIN4] 
Switch from where the RPM is measured. When source is Analog input the converted value is going to 
be in RPM range – see example below.