InteliDrive Lite, SW version 1.9  
ID-FLX-Lite-1.9r1 Reference Guide.pdf, ©ComAp – August 2015   
 Step:     1min 
Range:    1 - 1440min 
Default:   5min 
7.8.9  Timer2Function  [NoFunc,  AutoRun,  AutoRegCMP,  AutoBatt, 
AutoStop] 
No Func:  Operates just corresponding  LBO Timer2  according the Timer2 setting, see  Timer2 
repeat,  Time2  ON  time,  Timer2Duration.  Function  operates  in  all  OFF-MAN-AUT 
modes.  Default  state. 
 
AutoRun:   Engine automatically starts and stops in AUT mode (similar to LBI Rem start/stop, the 
same  record  in  the  history)  according  the  Timer2  setting. 
 
AutoRegCMP:  Start  and  stop  engine  in  AUT  mode  according  to  the  LBO  Speed  switch  -  see 
Regulator:  Reg  CMP  setpoints.  The  comparator  function  (output)  works  opposite 
when  Regulator:  Reg  CMP  On  <  Reg  CMP  Off.  The  Date/Time:  Timer2  repeat, 
Timer2  ON  time,  Timer2Duration  settings  are  not  important  in  this  case. 
 
AutoBatt:   Engine starts when actual Battery voltage < Engine protect: Batt undervolt + Batt volt 
del  and  stays  running  for  Date/Time:  Timer2  Duration.  Function  operates  in  AUT 
mode. 
 
AutoStop:  Engine is switched from AUT to MAN and stopped or stopped from MAN mode (like by 
STOP  button)  when  engine  runs  longer  then  Date/Time:  Timer2Duration  on  actual 
RPM less or equal Engine params: Idle speed + 5% (fix limit). Function is not active 
during engine start. 
7.8.10  Timer2repeat   [NONE, MONDAY, TUESDAY, WEDNESDAY, 
THURSDAY,  WEDNESDAY,  FRIDAY, 
SATURDAY,  SUNDAY,  MON-FRI,  MON-SAT, 
MON-SUN, SAT-SUN] 
This setpoint defines Timer2 activation. Binary output Timer2 is internally linked with Rem Start/Stop 
binary input. Refer to binary inputs for details. 
NONE:    Timer function is disabled. Defualt state. 
MONDAY, TUESDAY, WEDNESDAY, THURSDAY, WEDNESDAY, FRIDAY, SATURDAY, SUNDAY:       
Timer is activated on daily basis. 
MON-FRI, MON-SAT, SAT-SUN:  
Timer is activated on selected day interval. 
7.8.11  Timer2 ON time     [HH:MM:SS] 
Display day time when Timer 2 output is activated. 
7.8.12  Timer2Duration    [min] 
Adjusts duration of Timer 2 output. 
 Step:     1min 
Range:    1 - 1440min