InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf, ©ComAp – August 2015
108
Step: 1min
Range: 1 - 1440min
Default: 5min
7.8.9 Timer2Function [NoFunc, AutoRun, AutoRegCMP, AutoBatt,
AutoStop]
No Func: Operates just corresponding LBO Timer2 according the Timer2 setting, see Timer2
repeat, Time2 ON time, Timer2Duration. Function operates in all OFF-MAN-AUT
modes. Default state.
AutoRun: Engine automatically starts and stops in AUT mode (similar to LBI Rem start/stop, the
same record in the history) according the Timer2 setting.
AutoRegCMP: Start and stop engine in AUT mode according to the LBO Speed switch - see
Regulator: Reg CMP setpoints. The comparator function (output) works opposite
when Regulator: Reg CMP On < Reg CMP Off. The Date/Time: Timer2 repeat,
Timer2 ON time, Timer2Duration settings are not important in this case.
AutoBatt: Engine starts when actual Battery voltage < Engine protect: Batt undervolt + Batt volt
del and stays running for Date/Time: Timer2 Duration. Function operates in AUT
mode.
AutoStop: Engine is switched from AUT to MAN and stopped or stopped from MAN mode (like by
STOP button) when engine runs longer then Date/Time: Timer2Duration on actual
RPM less or equal Engine params: Idle speed + 5% (fix limit). Function is not active
during engine start.
7.8.10 Timer2repeat [NONE, MONDAY, TUESDAY, WEDNESDAY,
THURSDAY, WEDNESDAY, FRIDAY,
SATURDAY, SUNDAY, MON-FRI, MON-SAT,
MON-SUN, SAT-SUN]
This setpoint defines Timer2 activation. Binary output Timer2 is internally linked with Rem Start/Stop
binary input. Refer to binary inputs for details.
NONE: Timer function is disabled. Defualt state.
MONDAY, TUESDAY, WEDNESDAY, THURSDAY, WEDNESDAY, FRIDAY, SATURDAY, SUNDAY:
Timer is activated on daily basis.
MON-FRI, MON-SAT, SAT-SUN:
Timer is activated on selected day interval.
7.8.11 Timer2 ON time [HH:MM:SS]
Display day time when Timer 2 output is activated.
7.8.12 Timer2Duration [min]
Adjusts duration of Timer 2 output.
Step: 1min
Range: 1 - 1440min

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals