InteliDrive Lite, SW version 1.9  
ID-FLX-Lite-1.9r1 Reference Guide.pdf, ©ComAp – August 2015   
7.4.10  Cooling speed     [IDLE, NOMINAL] 
Selects the function of the Binary output IDLE/NOMINAL during engine Cooling state.  
IDLE:     Cooling is executed at Idle speed. 
NOMINAL:   Cooling is executed at Nominal speed. Default state. 
 
HINT 
Binary  output  IDLE/NOMINAL  must  be  configured  and  connected  to  speed  governor.  Engine  Idle 
speed must be adjusted on speed governor. 
7.4.11  Cooling time      [s] 
Run time of the unloaded engine to cool the engine before stop. 
Step:     1s 
Range:    0 - 3600s 
Default value:  30s 
7.4.12  AfterCool time     [s] 
Run time of engine after cooling pump. Binary output Cooling pump is closed when the engine starts 
and opens AfterCool time delayed after engine stops. 
Step:    1s 
Range:   0 - 3600s 
Default value:  180s 
7.4.13  Stop time      [s] 
Under normal conditions the engine must certainly stop within this period. The period starts by issuing 
stop command.  
Step:     1s 
Range:    0 - 240s 
Default value:  60s 
HINT 
Stop of engine is detected when all following conditions are met: RPM <2, Oil pressure < StartingPOil 
and D+ input isn’t active. 
Stop fail is detected if there is difference between those conditions. 
7.4.14  Fuel solenoid      [DIESEL, GAS] 
Setpoint setting determines behavior of the Binary output FUEL SOLENOID.  
DIESEL:  Output closes 1 sec before Binary output STARTER.  
The output opens if Emergency stop comes or Cooled engine is stopped and in pause 
between repeated starts. 
GAS:  In  this  mode  of  operation  the  output  closes  to  open  the  gas  valve  and  enable  the 
engine to start. The delay of Fuel solenoid output activation in relation to Starter output 
is defined by FuelSol offset. The output closes only if RPM > 30 (i.e. the starter motor 
is engaged).