124
10.2.19 ChrgAlternFail
Output closes if engine is running and D+ input not energized.
The output opens, if
alarm is not active and
FAULT RESET is pressed
HINT
Threshold level for D+ input is 80% supply voltage.
10.2.20 Stop failed
Output closes when the engine has to be stopped, but speed or oil pressure is detected. This
protection goes active 60s after stop command.
The output opens, if
alarm is not active and
FAULT RESET is pressed
10.2.21 Overspeed
Output closes if the engine over speed alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
10.2.22 Underspeed
Output closes if the engine “Sd Underspeed” alarm activates i.e. when RPM is below the Engine
params: Starting RPM limit.
The output opens, if
alarm is not active and
FAULT RESET is pressed
10.2.23 Start failed
Output closes after the engine start-up fails.
The output opens, if
alarm is not active and
FAULT RESET is pressed
10.2.24 Battery flat
Output closes when InteliDrive Lite performs reset during start procedure (probably due to weak
battery).
The output opens, if
alarm is not active and
FAULT RESET is pressed