InteliDrive Lite, SW version 1.9  
ID-FLX-Lite-1.9r1 Reference Guide.pdf, ©ComAp – August 2015   
Default value:  5s 
7.4.6  CrnkFail pause      [s] 
Pause between crank (engine start) attempts.  
Step:     1s 
Range:    5 - 60s 
Default value:  8s 
7.4.7  Crank attempts      [-] 
Maximum number of crank (engine start) attempts.  
Step:     1 
Range:    1 - 10 
Default value:  3 
7.4.8  Idle time         [s] 
Idle time delay starts when RPM exceeds Start RPM. Start fail is detected when during Idle state RPM 
decreases below 2.  
During the Idle time timer running the binary output IDLE/NOMINAL is opened, when it expires the 
IDLE/NOMINAL output closes.  Binary output IDLE/NOMINAL opens during Cooling period again. 
Note: 
Engine can be switched between Idle and Running state by Binary input Nominal/Idle in MAN mode. 
Step:     1s 
Range:    0 - 600s 
Default value:  12s 
 
7.4.9  Idle speed          [RPM] 
Speed request in engine Idle state i.e. after engine start or when switched to Idle in MAN mode by 
Binary input Nominal/Idle and after Engine ShutDown.  
Step:     1RPM 
Range:    Starting RPM – MinSpeedLimit 
Default value:  800RPM