InteliDrive Lite, SW version 1.9  
ID-FLX-Lite-1.9r1 Reference Guide.pdf, ©ComAp – August 2015   
6 Function description 
6.1  Engine operation states 
Auto test during controller power on  
Engine is not ready to start 
Prestart sequence in process, Prestart output is closed 
Pause between start attempts 
Starting speed  is reached and the Idle timer is running 
Engine is running at nominal speed 
Shut-down alarm activated 
Engine is cooling before stop 
Emergency Manual engine operation 
Engine after cooling - Cooling Pump output is closed 
6.2  OFF mode 
No start of the engine is possible. Outputs STARTER and FUEL SOLENOID are not energized.  No 
reaction if START, STOP buttons are pressed. 
6.3  MAN mode 
START - starts the engine. 
STOP - stops the engine. 
HINT 
The engine can run without load unlimited time. 
The controller does not automatically stop the running engine in MAN mode. 
The controller does not start the engine when binary input REM START/STOP is closed.  
6.3.1  Start-stop sequence (simplified) 
MODE = MAN (Engine start/stop request is given by pressing buttons START and STOP)  
MODE = AUT (Engine start/stop request is given by binary input REM START/STOP) 
Condition of the transition 
PRESTART on 
Prestart time counter started 
RPM > 2 or Oil pressure detected or D+ 
is active