EasyManua.ls Logo

ComAp InteliDrive Lite - AIN2 Level 1 [ ]; AIN2 Level 2 [ ]; AIN2 del [S]; AIN3 Level 1 [ ]

ComAp InteliDrive Lite
149 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf, ©ComAp August 2015
95
7.7.12 AIN2 Level 1 [ ]
Warning limit level for ANALOG INPUT 2
Step: 1C
Range: -100 - 10000°C
Default: 80°C
7.7.13 AIN2 Level 2 [ ]
Shutdown limit level for ANALOG INPUT 2
Step: 1C
Range: -100 - 10000°C
Default: 90°C
7.7.14 AIN2 Del [s]
Delay for ANALOG INPUT 2 alarm.
Step: 1s
Range: 0 - 180s
Default: 5s
NOTE:
Analog input 2 is usually determined to Engine Temperature measurement and it is resistive type of
input with range 0-2500Ohm.
7.7.15 AIN3 Level 1 [ ]
Warning limit level for ANALOG INPUT 3
Step: 1 %
Range: -100 - +10000%
Default: 20%
7.7.16 AIN3 Level 2 [ ]
Shutdown limit level for ANALOG INPUT 3
Step: 10%
Range: -100 - +10000%
Default: 10%
7.7.17 AIN3 Del [s]
Delay for ANALOG INPUT 3
Step: 1s
Range: 0 - 180s
Default: 10s
NOTE: