3.4.3 IL-NT AIO
IL-NT AIO is optional plug-in card. This card offers additional four analog inputs and one analog
output. Analog inputs can be use for different types of sensor (resistive, current and voltage) and
variable analog output, which can be used as PWM. Adjustment of extension plug-in modul is possible
via LiteEdit too.
Type of analog input is selectable by jumper. Each analog input has own line of jumper position. The
top position (closest to green conector on the pic above) is for resistive input, central position for
voltage input and lowest position is for current input.
AI1 AI4
2600 Ohm / 4V / 20 mA
Iout
Uout
PWM
0 20 mA (max 22mA) max 100 Ohm load
0 4,5V (max 10mA)
PWM 5V / 15mA / 500 Hz
Not used
Do not connect!