InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf, ©ComAp – August 2015
Step: 1s
Range: 0 - 3600s
Default: 0s
HINT
The corresponding BIN protection has to be configured as Running only in LiteEdit.
7.7.73 DEF Level Min [%]
Diesel Exhaust Fluid level protection activates LBO DEF Tank Level when received level (J1939 -
SCR - Selective Catalytic Reduction message) is below DEF Level Min for more than (fix) 3s delay.
This function is active for IVECO NEF&&Cursor engine. LBO can be active for running engine only.
Step: 1%
Range: 0 - 150%
Default: 10%
7.7.74 DEF Level Max [%]
Diesel Exhaust Fluid level protection deactivates LBO DEF Tank Level when received level (J1939 -
SCR - Selective Catalytic Reduction message) is above DEF Level Max for more than (fix) 3s delay.
This function is active for IVECO NEF&&Cursor engine.
Step: 1%
Range: 0 - 150%
Default: 90%
NOTE:
DEF Level is usual signage of Urea tank level, which is more often used in United States.
7.8 Date/Time
7.8.1 Time stamp per [min]
This setpoint is dedicated to adjustment of time interval for periodical history records.
Step: 1min
Range: 0 - 200min
Default: 60min
7.8.2 SummerTimeMod [DISABLED, WINTER, SUMMER, WINTER-S,
SUMMER-S]
DISABLED: Automatic switching between summer and wintertime is disabled.
WINTER (SUMMER): Automatic switching between summer and winter time is enabled and
it is set to winter (summer) season.
WINTER-S (SUMMER-S) : Modification for southern hemisphere.