InteliDrive Lite, SW version 1.9  
ID-FLX-Lite-1.9r1 Reference Guide.pdf, ©ComAp – August 2015   
Step:     1s 
Range:   0 - 3600s 
Default:   0s 
HINT 
The corresponding BIN protection has to be configured as Running only in LiteEdit.  
7.7.73  DEF Level Min   [%] 
Diesel Exhaust Fluid  level  protection  activates  LBO DEF Tank Level  when received level  (J1939  - 
SCR - Selective Catalytic Reduction message) is below DEF Level Min for more than (fix) 3s delay. 
This function is active for IVECO NEF&&Cursor engine. LBO can be active for running engine only. 
Step:    1% 
Range:   0 - 150% 
Default:   10% 
7.7.74  DEF Level Max   [%] 
Diesel Exhaust Fluid level protection deactivates LBO DEF Tank Level when received level (J1939 - 
SCR - Selective Catalytic Reduction message) is above DEF Level Max for more than (fix) 3s delay. 
This function is active for IVECO NEF&&Cursor engine.  
Step:    1% 
Range:   0 - 150% 
Default:   90% 
NOTE: 
DEF Level is usual signage of Urea tank level, which is more often used in United States.  
7.8  Date/Time 
7.8.1  Time stamp per     [min] 
This setpoint is dedicated to adjustment of time interval for periodical history records. 
Step:     1min 
Range:    0 - 200min 
Default:   60min 
7.8.2  SummerTimeMod  [DISABLED,  WINTER,  SUMMER,  WINTER-S, 
SUMMER-S] 
DISABLED:      Automatic switching between summer and wintertime is disabled. 
WINTER (SUMMER):    Automatic switching between summer and winter time is enabled and 
it is set to winter (summer) season. 
WINTER-S (SUMMER-S) :   Modification for southern hemisphere.