Chapter 4 Analog Input/Output Module AH06XA
4-19
*5. If the ripple voltage of the input terminal of the load connected is large, and results in interference with
the wiring, please connect a 0.1~0.47 μF and 25 V capacitor.
*6. Please connect the ground wire in the shielded cable to the terminal SG.
*7. Once AH06XA-5A is installed on a backplane, the connection between the terminal SG on
AH06XA-5A and the terminal on the backplane will be a short circuit. Please connect the terminal
on the backplane to the ground terminal .
4.3.4 LED Indicators
Number Name Description
1
RUN LED
indicator
Operating status of the module
ON: The module is running.
OFF: The module stops running.
2
ERROR LED
indicator
Error status of the module
ON: A serious error occurs in the module.
OFF: The module is normal.
Blink: A slight error occurs in the module.
4.4 HWCONFIG in ISPSoft
4.4.1 Initial Setting
(1) Start ISPSoft, and then double-click HWCONFIG.