AH500 Module Manual 
10-6 
10.2.4  Address Switch 
The switch is used on setting up the node address of AH10DNET-5A on DeviceNet. Range: 00~63 
(64~99 are forbidden.) 
Switch setting  Description 
0-63 
Valid DeviceNet node address 
64-99 
Invalid DeviceNet node address
 
Example: If you need to set the node address of AH10DNET-5A to 26, simply switch the 
corresponding switch of x10
1
 to 2 and the corresponding switch of x10
0
 to 6. 
Note: 
1.  After the setup is completed, repower AH10DNET-5A. While AH10DNET-5A is working, 
changing the setting of node address will be invalid. 
2.  Use the slotted screwdriver to rotate the switch carefully in case you scratch the switch. 
10.2.5  Function Switch 
The function switches are used for: 
  Setting up the work mode (IN0) 
  Setting up the baud rate of DeviceNet (DR0~DR1) 
Max. transmission distance 
 
ON  OFF  500 kbps  100 m 
ON  ON 
Entering the mode of extended baud rate (See 
section 10.7.3.) 
IN0 
ON 
When the corresponding equipment is off-line, 
the I/O data in the buffer area will be held. 
OFF 
When the corresponding equipment is off-line, 
the I/O data in the buffer area will be cleared. 
Reserved 
Note: 
1.  After the setup of the function switch including DR1, DR0 and IN0 is completed, repower 
AH10DNET-5A. 
2.  Use slotted screwdriver to adjust the DIP switch carefully in case you scratch the switch. 
10.2.6  Seven-segment Display 
The digital display provides the following function: 
  Showing the node station number of AH10DNET-5A 
  Showing the error message of the slave 
Note: 
1.  While AH10DNET-5A is working normally, the digital display shows its own node address. 
2.  If “E1” and “03” are shown continuously, it indicates that the error of E1 exists in the slave of 
node address 03. 
3.  If the error codes such as “E7” and “E1” are shown, please refer to section 10.10.2 for 
treatment. 
10.2.7  Backplane Interface 
The interface is used for connection between AH10DNET-5A and a backplane.