AH500 Module Manual
11-12
Tighten the screw of the communication connector to
fix the cable to the holes of the connector with a
standard slotted screwdriver.
11.3.4 Installing the DeviceNet Connector
After wiring is over, insert the DeviceNet connector to the interface.
Tighten the screws of the two sides of the DeviceNet terminals.
Note:
The cable should be away from the power wire to decrease the electromagnetic interference.
The two ends of the shielded wire should be grounded.
The 121 ohm resistor should be connected between the white and blue signal wires.
11.3.5 DeviceNet Bus Transmission Distance and Network
Topology Structure
DeviceNet bus transmission distance is determined by the DeviceNet bus transmission speed.
See the following table on different transmission speed and the corresponding maximum
communication distance.
speed (bit/second)
10K 20K 50K 125K 250K 500K 800K 1M
communication
distance
5000 2500 1000 500 250 100 50 25