AH500 Module Manual 
2-16 
3.  The terminal block is removed. 
  AH04AD-5A/AH08AD-5B/AH08AD-5C    AH08AD-5A 
 
 
 
2.3.3 Wiring 
  Precautions 
In order to make the functions of an analog-to-digital module perfect and ensure the reliability of 
a system at the same time, external wiring which prevents noise is necessary. Before installing 
cables, users need to follow the precautions below. 
(1)  To prevent a surge and induction, an AC cable and input signal cables which are connected 
to AH04AD-5A/AH08AD-5A/AH08AD-5B/AH08AD-5C must be separate cables. 
(2)  A cable must not be installed near a main circuit, a high-voltage cable, or a cable connected 
to a load which is not a PLC. Besides, a cable must not be bound to a main circuit, a 
high-voltage cable, or a cable connected to a load which is not a PLC. Otherwise, effects 
that noise, induction, and a surge have will increase.   
(3)  Please connect a shielded cable and a hermetically sealed cable with the ground 
separately. 
(4)  Terminals with insulation sleeves can not be arranged as a terminal block. It is 
recommended that the terminals be covered with insulation tubes. 
(5)  Please connect 30 to 24 AWG (0.3 to 0.6 mm) wires to the input/output terminals. The 
lengths of the plastic jackets which are removed from the cables used should be in the 
range of 7 mm to 8 mm. The specifications for the terminals and the wiring of the terminals 
are shown below. Only copper leads which can resist the heat above 60°C can be used. 
30-24AWG
 0.3-0.6mm
 
 
(6)  Two-wire connection/Three-wire connection/Four-wire connection: 
  Two-wire connection/Three-wire connection (Passive transducer): A transducer and an 
analog input module are connected to a power circuit collectively. 
  Four-wire connection (Active transducer): A transducer uses an independent power 
supply. It is not connected to the power circuit which is connected to an analog input 
module.