AH500 Module Manual 
10-14 
10.4  Configuration of AH10DNET-5A 
10.4.1  Data Mapping Areas 
This section is going to introduce the mapping relations between an AH500 series CPU module and 
AH10DNET-5A. 
 
 
An AH500 series CPU module can be extended by connecting maximum 8 AH10DNET-5A scanner 
modules which could only be installed to the main backplane. After AH10DNET-5A and an AH500 
series CPU module is connected, users could specify the starting register addresses for the input 
mapping and output mapping. 
When only one backplane exists and there are several AH10DNET-5As on the right side of an 
AH500 series CPU module, the software distinguishes different AH10DNET-5As according to their 
unit numbers. The farther the scanner module is away from an AH500 series CPU module, the 
larger its unit number is. The unit number of the first AH10DNET-5A of the right side of an AH500 
series CPU module is 1. The next one nearest to the first scanner module is 2. And the following 
ones will be 3, 4 and so on. 
10.4.2  Assignment of Mapping Area (in Master Mode) 
While AH10DNET-5A works in master mode and the starting addresses for output and input are 
specified as D500 and D1000 respectively, the mapping area will be assigned as the following table 
is. 
Input area: Slave->Master 
Output area: Master->Slave 
CPU module 
Register No.
Purpose 
Data 
Length 
CPU module 
Register No. 
Purpose 
Data 
Length 
D1000~D1003 
status display 
area (See section 
10.6.1.) 
4 words  D500~D503 
command area 
(See section 
10.5.) 
4 words 
D1004 
Scanner module 
status display 
area (See section 
10.6.2.) 
1 word  D504  Reserved  1 word 
D1005~D1494 
data area: these 
registers are used 
for receiving the 
status data 
feedback from the 
slave. 
Max. 
length: 
words 
D505~D994 
DeviceNet output 
data area: the 
values in these 
registers are sent 
to the slave as 
the control data. 
Max. 
length: 
words 
Note: D1000 and D500 in the above table are the starting addresses in the mapping area. If the 
addresses are set to other registers, the corresponding function will be assigned to other 
registers.   
 
If the length of DeviceNet input data area is 3 words, AH10DNET-5A will occupy D1000~D1004 and 
D1005~D1007 in an AH500 series CPU module automatically. Meanwhile, if the length of DeviceNet 
output data area is 2 words, AH10DNET-5A will occupy D500~D504 and D505~D506 in an AH500 
series CPU module automatically.