EasyManua.ls Logo

Delta AH500 - Connecting to the Devicenet Communication Connector; Devicenet Bus Network Topology Structure

Delta AH500
780 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AH500 Module Manual
10-8
10.3.2 Connecting to the DeviceNet Communication Connector
1. After wiring is completed, insert the DeviceNet connector to the port.
2. Tighten the screws on two sides of the DeviceNet terminal.
10.3.3 DeviceNet Bus Network Topology Structure
The transmission distance on the DeivceNet bus network is determined by the transmission rate.
The following table shows the corresponding maximum communication distance at different baud
rates.
Baud rate (Bit/s)
10K 20K 50K 125K 250K 500K 800K 1M
Max. transmission
distance (M)
5000 2500 1000 500 250 100 50 25