AH500 Module Manual
2-32
2.5 Troubleshooting
2.5.1 Error Codes
Error
Code
Type Description
RUN LED
indicator
ERROR
LED
indicator
16#A600 Alarm Hardware failure OFF ON
16#A601 Alarm The external voltage is abnormal. OFF ON
16#A603 Alarm
Internal error
The factory correction is abnormal.
OFF ON
16#A400 Alarm
The signal received by channel 0 exceeds the range
of inputs which can be received by the hardware.
OFF ON
16#A401 Alarm
The signal received by channel 1 exceeds the range
of inputs which can be received by the hardware.
OFF ON
16#A402 Alarm
The signal received by channel 2 exceeds the range
of inputs which can be received by the hardware.
OFF ON
16#A403 Alarm
The signal received by channel 3 exceeds the range
of inputs which can be received by the hardware.
OFF ON
16#A404 Alarm
The signal received by channel 4 exceeds the range
of inputs which can be received by the hardware.
OFF ON
16#A405 Alarm
The signal received by channel 5 exceeds the range
of inputs which can be received by the hardware.
OFF ON
16#A406 Alarm
The signal received by channel 6 exceeds the range
of inputs which can be received by the hardware.
OFF ON
16#A407 Alarm
The signal received by channel 7 exceeds the range
of inputs which can be received by the hardware.
OFF ON
16#A000 Warning
The signal received by channel 0 exceeds the range
of inputs which can be received by the hardware.
ON Blink
16#A001 Warning
The signal received by channel 1 exceeds the range
of inputs which can be received by the hardware.
ON Blink
16#A002 Warning
The signal received by channel 2 exceeds the range
of inputs which can be received by the hardware.
ON Blink
16#A003 Warning
The signal received by channel 3 exceeds the range
of inputs which can be received by the hardware.
ON Blink
16#A004 Warning
The signal received by channel 4 exceeds the range
of inputs which can be received by the hardware.
ON Blink
16#A005 Warning
The signal received by channel 5 exceeds the range
of inputs which can be received by the hardware.
ON Blink
16#A006 Warning
The signal received by channel 6 exceeds the range
of inputs which can be received by the hardware.
ON Blink
16#A007 Warning
The signal received by channel 7 exceeds the range
of inputs which can be received by the hardware.
ON Blink
16#A800 Warning
The signal received by channel 0 exceeds the range
of inputs which can be received by the hardware.
ON OFF
16#A801 Warning
The signal received by channel 1 exceeds the range
of inputs which can be received by the hardware.
ON OFF
16#A802 Warning
The signal received by channel 2 exceeds the range
of inputs which can be received by the hardware.
ON OFF
16#A803 Warning
The signal received by channel 3 exceeds the range
of inputs which can be received by the hardware.
ON OFF
16#A804 Warning
The signal received by channel 4 exceeds the range
of inputs which can be received by the hardware.
ON OFF