Chapter 11 DeviceNet Remote I/O Module AHRTU-DNET
11-109
11.7.4 Diagnosis by Software
On the main interface of AHRTU-DNET-5A configuration, click “Diagnose” and then the related
information will be shown on the diagnosis data area.
0x8001
AHRTU-DNET-5A was
unable to detect the
configured module.
1. Check if the connection between the module
and the rack is loose so that the connection is
broken.
2. Check is the module is damaged.
0x8002
The current module does not
fit the configured module.
Ensure that the actually connected module and the
module configured in the software are identical.
Notes:
For other error codes, please refer to the user manual of the related module.
The software diagnosis function can be started up only when the DeviceNet Builder software is
online.