AH500 Module Manual 
12-2 
12.1  Introduction to AH10PFBM-5A 
AH10PFBM-5A runs on the right side of AH500 series PLC and constitutes the PROFIBUS DP 
master with AH500 series PLC together. 
12.1.1  Features 
  While using AH10PFBM-5A, the power module PS05 and the main rack and etc are 
necessary for AH10PFBM-5A to be used together.   
  No external power is needed since the rack can provide the power to AH10 PFBM-5A. 
  AH10PFBM-5A can not be inserted to the I/O slot of the extension rack except the AH main 
rack. 
  Maximum 8 AH10 PFBM-5A modules can be connected to the main rack. 
  Supports the hot plug function (The module can be inserted to the I/O slot or be removed 
from the I/O slot when the main rack is powered on) 
  Please read the manual carefully before use. The manual merely provides the information 
on specification, functions and trouble-shooting of the product excluding the details on the 
PROFIBUS DP protocol. For more details on the PROFIBUS DP protocol, please refer to 
relevant professional articles or literatures. 
12.1.2  Introduction 
AH10PFBM-5A can be used as the class-1 DP master only with the following functions. 
  Supports DPV0. That is, the master and slave make the exchange
 periodically. It supports 
maximum 2880 words of input data and 2880 words of output data. 
  Supports DPV1 (The slave supporting DPV1 is needed). The master can read/write the data 
in the slave periodically via the read/write function of DPV1 provided by ISPSoft. 
  The module automatically exchanges the data with AH500 series PLC. User can directly 
operate the specified registers in AH500 series PLC so as to achieve to control and monitor 
the slave. 
  Supports multiple kinds of diagnosis such as the digital displays, indicators, specified 
registers and software to detect the troubles of the module and slave. 
  Supports the communication rate ranging 9.6Kbps~12Mbps. 
  Able to connect maximum 125 slaves and its node address can be set to 0~125 through 
SYCON.net and the node address of the slave can be set to 1~125. If the hardware actually 
connected to the network is over 32, or out of the distance that the corresponding baud rate 
allows, the RS-485 repeater is necessary to be added to expand the physical network. 
  The network configuration software(SYCON.net)provides the easy and handy graphic 
configuration interface to automatically scan and recognize all slaves on the network.
 
12.1.3  Specifications 
  AH500 CPU supported 
Item  Specification 
Model name  AH500 series PLC 
  PROFIBUS DP interface 
Item  Specification 
Interface 
DB9 connector 
Transmission method 
High-speed RS-485 
Transmission cable 
Two-wire twisted shielded cable 
Electrical isolation 
500 VDC