Chapter 12  Network Module  AH10PFBM 
12-57 
12.7.4  Error Codes of PROFIBUS Network on PLC System Log 
Read via ISPSoft  
Select menu “PLC”-> “System Log” to check the system log when ISPSoft is in monitor state. 
Explanation of error codes of PROFIBUS network on the PLC system log. 
Explanation  Treatment 
16#A4E2 
AH10PFBM-5A detects that 
one slave is offline. 
1. Detect if the PROFIBUS DP bus connection is 
proper. 
2. Detect if both ends of the network have 
connected the terminal resistors respectively. 
16#A4E6 
connected to AHRTU-PFBS-
5A is detected by the master. 
Please check the modules connected to AHRTU-
PFBS-5A. 
16#A001 
master module is empty. 
Download the appropriate configuration. 
16#A402 
PLC does not assign the IO 
mapping area to the master 
Assign the appropriate IO mapping area to the 
master via ISPSoft 
Just re-power it. 
16#A404  Master initializing error 
Contact the factory if the error still exists after re-
powering 10PFBM. 
16#A005 
communication between 
Contact the factory if the error still exists after re-
downloading the appropriate configuration. 
16#A406 
Internal storage unit error 
Contact the factory if the error still exists after re-
powering 10PFBM. 
16#A407 
Data exchange unit error 
Contact the factory if the error still exists after re-
powering 10PFBM. 
16#A408 
the master serial number 
detection error 
Contact the factory if the error still exists after re-
powering 10PFBM. 
16#A00B 
Timeout for the data 
exchange with PLC 
Contact the factory if the error still exists after re-
powering 10PFBM.