AH500 Module Manual
12-56
Item
value
Description Treatment
error
of
communicator
error
- Reserved -
slaves
-
configured in the master.
-
Active slaves -
communicating with the
master normally.
-
15…0
-
that the error on the slaves
(of number 1~125) occurs
such as offline, the
corresponding bit becomes
1. (Here there are totally 128
(0~127) bits assigned. Since
the node addresses of the
slaves can not be 0, 126 and
127, the corresponding bit
has no meaning.) Otherwise,
it is 0.
For more details, see the
following table on the error
slaves.
1. Check if the PROFIBUS DP bus
is connected correctly.
2. Check if either end of the
network is added with the terminal
resistor.
31…16
……
Error slaves
127…112
Corresponding relation table for error slaves:
Description Corresponding register
corresponding slave device
(
)
15~0
Error slaves 31…16
(
)
31~16
Error slaves 127…112
(
)
127~112