AH500 Module Manual
7-20
The conversion results are shown in the following table.
N kHz N kHz
0
The setting of the frequency
of an input pulse is disabled.
10 5.187988
1 2656.2504 11 2.593994
2 1328.1252 12 1.296997
3 664.0626 13 0.648499
4 332.0313 14 0.324249
5 166.0156 15 0.162125
6 83.00781 16 0.081062
7 41.50391 17 0.040531
8 20.75195 18 0.020266
9 10.37598 19 0.010133
2. If the value in CR#2 is 0, the external input terminals do not filter pulses. If the value in CR#2 is
larger than 19, the value will be counted as 0. For example, if the value in CR#2 is 10, the filter
coefficient is
5.187988
2
85000
410
(KHz). That is, the input signals whose frequencies are larger
than 5.187988 kHz are filtered out.
3.
7.9.4 Cycle of Reading the Number of Pulses
CH0 CH1 CH2 CH3
High word Low word High word Low word High word Low word High word Low word
- #3 - #31 - #59 - #87
[Description]
If bit 0 in CR0/CR28/CR56/CR84 is turned from OFF to ON, the number of pulses received by the
input terminals will be read according to the cycle set. The setting of a cycle is shown below.
Item Setting value
Cycle of reading the number of pulses 1~1000 (Unit: ms)
If the setting value is larger than 1000, the cycle will be counted as 1000 milliseconds. If the setting
value is less than 1, the cycle will be counted as 1 millisecond.
7.9.5 Counting Parameters
CH0 CH1 CH2 CH3
High word Low word High word Low word High word Low word High word Low word
- #4 - #32 - #60 - #88
[Description]
Bit 0~bit 15 are described below.
bit# Description
0
Setting the polarities of the input contacts
OFF: Normally-open contacts
ON: Normally-closed contacts
1
Setting the function of prescaling the number of input pulses
OFF: The function is disabled.
ON: The function is enabled.
2
Setting the function of averaging the number of sampled pulses
OFF: The function is disabled.
ON: The function is enabled.
3 Setting the alarm function