AH500 Module Manual 
8-2 
8.1  Introduction 
Thanks for using AH10/15SCM-5A, a serial communication module. To ensure that 
AH10/15SCM-5A is installed and operated correctly, please read this manual carefully before using 
the module. 
AH10/15SCM-5A is a serial communication module. It supports the Modbus UD Link (user-defined 
format). It can function as a BACnet MS/TP slave. A BACnet MS/TP master can read an analog 
value/binary value from AH10/15SCM-5A, and can write an analog value/binary value into 
AH10/15SCM-5A. Besides, it can be used as a RS-485/RS-422/RS-232 communication port 
through which a program is downloaded to or uploaded from a CPU module. AH10/15SCM-5A is set 
by means of SCMSoft in DCISoft. Please use DCISoft version 1.18 or above. 
 
Functions: 
  It is equipped with two RS-485/RS-422 ports (COM1 & COM2) (application for AH10SCM-5A). 
  It is equipped with two RS-232 ports (COM1 & COM2) (applicable for AH15SCM-5A). 
  There is isolation between two parts of RS-485/RS-422 communication, and there is isolation 
between two parts of power (application for AH10SCM-5A). 
  There are two built-in switches of 120 Ω terminal resistors (application for AH10SCM-5A). 
  Every communication port can be connected to 32 devices at most. 
  It can function as COM3 through which a program is downloaded or uploaded. 
  Modbus Advance provides a means of exchanging data through Modbus. 
  The UD Link provides a user-defined communication protocol, and a sequence-planning 
function. 
  It can function as a BACnet MS/TP slave, and can be connected to a master. 
 
The functional specifications 
  RS-485/RS-422 communication interface (application for AH10SCM-5A) 
European-style terminal block 
 
1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 76,800, 115,200, 
230,400, and 460,800 bps 
Communication 
format 
Stop bit: 1 bit and 2 bits 
Parity bit: none, an odd parity bit, and an even parity bit 
Data bit: 7 bits and 8 bits 
Communication 
protocol 
UD Link 
BACnet MS/TP slave stations 
 
  RS-232 communication interface (application for AH15SCM-5A) 
 
1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800, 115200 bps 
Communication 
format 
Stop bit: 1 bit and 2 bits 
Parity bit: none, an odd parity bit, and an even parity bit 
Data bit: 7 bits and 8 bits 
Communication 
protocol 
Modbus ASCII/RTU 
UD Link 
BACnet MS/TP slave stations