EasyManua.ls Logo

Delta AH500 - 2.2 Specifications and Functions; 2.2.1 Specifications

Delta AH500
780 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AH500 Module Manual
2-2
2.1 Overview
The specifications for analog-to-digital modules, the operation, and the programming are described
in this chapter. AH04AD-5A, AH08AD-5A, AH08AD-5B, and AH08AD-5C are analog-to-digital
modules.
2.1.1 Characteristics
(1) A module is selected according to practical application.
AH04AD-5A: There are four channels. Inputs received by a channel can be either voltages or
currents.
AH08AD-5A: There are eight channels. Inputs received by a channel can be either voltages or
currents.
AH08AD-5B: There are eight channels. Inputs received by these channels are voltages.
AH08AD-5C: There are eight channels. Inputs received by these channels are currents.
(2) High-speed conversion
An analog signal is converted into a digital signal at a speed of 150 μs a channel.
(3) High accuracy
Conversion accuracy: The error is ±0.1% of an input voltage, and ±0.1% of an input current.
(The ambient temperature is 25°C. The number of input voltages/currents
which are averaged is 100.)
(4) A scale range can be set by means of software.
Users can set a scale range in ISPSoft. A scale range is a range of digital values to which a
range of analog values corresponds.
(5) A module can be set by means of utility software.
HWCONFIG is built-in utility software in ISPSoft. Users can set modes and parameters in
HWCONFIG to complete hardware configuration without spending time writing a program to set
registers corresponding to functions.
2.2 Specifications and Functions
2.2.1 Specifications
Electrical specifications
Module name AH04AD-5A AH08AD-5A AH08AD-5B AH08AD-5C
Number of inputs
4 8 8 8
Analog-to-digital
conversion
Voltage input/
Current input
Voltage input/
Current input
Voltage input Current input
Supply voltage
24 V DC (20.4 V DC~28.8 V DC) (-15%~+20%)
Connector type
Removable terminal block
Conversion time
150 μs/channel
Isolation
An analog circuit is isolated from a digital circuit by a digital integrated
circuit/an optocoupler, but the analog channels are not isolated from one
another.
Isolation between a digital circuit and the ground: 500 V DC
Isolation between an analog circuit and the ground: 500 V DC
Isolation between an analog circuit and a digital circuit: 500 V DC
Isolation between the 24 V DC and the ground: 500 V DC

Table of Contents