AH500 Module Manual 
8-46 
8.7.2  Connecting to ISPSoft 
AH10/15SCM-5A can be used as an additional communication port for an AH500 series CPU 
module. ISPSoft can be connected to the AH500 series CPU module through a communication port 
on AH10/15SCM-5A. The default communication format of COM1 on AH10/15SCM-5A is “9600, 7, 
Even, 1”. The slave ID is 247. 
(1)  Setting ISPSoft 
Start ISPSoft, and click Communication Settings… on the Tools menu. 
 
 
(2)  Select Driver1 in the Driver box. (The communication format of COM1 set by COMMGR is 
“9600, 7, Even, 1”.) Please notice that the station address in the Communication Setting 
window must be the same as the slave ID set for COM1. The station address is not the station 
address of the AH500 series CPU module. 
 
 
(3)  After users click OK, a program can be downloaded to or uploaded from the AH500 series CPU 
module.