AH500 Module Manual 
15-36 
  ERROR LED indicator 
The red light flashes 
once. 
Bus fault 
1.  Check whether the CANopen bus 
cable used is a standard cable. 
2.  Check whether the both ends of 
the CANopen bus used are 
connected to terminal resistors.   
3.  Check whether the noise around 
the CANopen bus cable used is 
strong.   
The red light flashes 
twice. 
Master station: The control of 
the errors in a slave station is 
not sent after a set period of 
time. 
Slave station: AH10COPM-5A 
does not send a heartbeat 
message after a set period of 
time.   
1.  Check whether the CANopen bus 
cable used is a standard cable. 
2.  Check whether the both ends of 
the CANopen bus used are 
connected to terminal resistors. 
The red light is ON.  The bus used is off. 
1.  Check whether the bus cable on 
the CANopen network created is 
connected correctly. 
2.  Check whether the serial 
communucation speed of 
AH10COPM-5A is the same as the 
serial communication speeds of 
other slave stations. 
 
Difference between the red light which flashes once and the red light which flashes twice: 
ON
OFF
200 ms
1000 ms
The red light flashes once.
 
 
ON
OFF
200 ms
200 ms
200 ms
1000 ms
The red light flashes twice.
 
 
15.6.2  Error Codes 
Users can monitor the error codes in the system log in ISPSoft, or the error code in the module error 
code register in the AH500 series CPU module used.
 
  AH10COPM-5A functions as a master station. 
16#A0E0 
AH10COPM-5A receives an emergency 
message from a slave station. 
CANopen_EMCY to read relevant 
information. 
16#A0E1 
The length of a PDO that a slave station 
sends is not the same as the length of the 
PDO set in the node list. 
Set the length of the PDO in the 
slave station again, and then 
download the setting to 
AH10COPM-5A.