AH500 Module Manual
1-4
1.2 Specifications
1.2.1 General Specifications
Item
Specifications
Operating
temperature
-20~60°C
Storage temperature
-40~70°C
Operating humidity
5~95%
No condensation
Storage humidity
5~95%
No condensation
Vibration/Shock
resistance
International standards IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2
& IEC 68-2-27 (TEST Ea)
Work environment
No corrosive gas exists.
Installation location
In a control box
Pollution degree
2
1.2.2 EMC Standards
1.2.2.1 EMI
Port
Frequency range
Level (Normative)
Reference standard
Enclosure port
(radiated)
(measured at a
distance of 10
meters)
30-230 MHz 40 dB (μV/m) quasi-peak
IEC 61000-6-4
230-1000 MHz 47 dB (μV/m) quasi-peak
AC power port
(conducted)
0.15-0.5 MHz
79 dB (μV) quasi-peak
IEC 61000-6-4
66 dB (μV) average
0.5-30 MHz
73 dB (μV) quasi-peak
60 dB (μV) average
1.2.2.2 EMS
Environmental
phenomenon
Reference standard Test Test level
Electrostatic
discharge
IEC 61000-4-2
Contact ±4 kV
Air
±8 kV
Radio frequency
electromagnetic
field
Amplitude
modulated
IEC 61000-4-3
80% AM,
1 kHz
sinusoidal
2.0-2.7 GHz 1 V/m
1.4-2.0 GHz 3 V/m
80-1000 MHz 10 V/m
Power frequency
magnetic field
IEC 61000-4-8
60 Hz 30 A/m
50 Hz 30 A/m