AH500 Module Manual 
8-18 
8.4.2  Introduction of the Related Instructions 
After AH10/15SCM-5A is installed, users need to write a program to control the related functions of 
AH10/15SCM-5A. The users can read data from a control register in AH10/15SCM-5A by means of 
the instruction FROM, and write data into a control register AH10/15SCM-5A by means of the 
instruction TO. 
API 
Instruction code  Operand  Function 
1400  D  FROM  P 
m
1
,
 
m
2
,
 
m
3
,
 
D
1
,
 
D
2
,
 
n 
Reading the data from the control 
register in the special module 
Device 
X  Y  M  S  T  C  HC  D  L  SM  SR  E  PR  K  16#  “$” 
DF 
1
2
   
     
   
m
3
 
   
     
   
1
   
   
         
     
 
       
D
2
 
   
   
         
     
 
       
 
Pulse instruction  16-bit instruction (13 steps)  32-bit instruction (13 steps) 
 
AH500  AH500  AH500 
Symbol: 
 
m
1
 
: 
Rack code  Word/Double word 
m
2
 
: 
Slot code  Word/Double word 
m
3
 
: 
Control register number  Word/Double word 
D
1
 
: 
Device in which the data is 
stored 
Word/Double word 
D
2
 
: 
Device in which the error 
code is stored 
Word/Double word 
n 
: 
Data length  Word/Double word 
Explanation: 
1.  Users can use this instruction to read the data from the control register in the special module 
into the AH500 series PLC. 
2.  The operand m
1
 should be in the range of 1 to 8. 1 represents a main rack, and 2~8 represent 
extension racks. 
3.  The operand m
2
 should be in the range of 0 to 11. If the rack code is 1, the slot code should be 
in the range of 0 to 11. If the rack code is in the range of 2 to 8, the slot code should be in the 
range of 0 to 7. 
4.  The operand m
3
 specifies the control register number. 
5.  When the instruction FROM is executed, D
2
 is set to 0. When an error occurs, D
2
 is not set to 0. 
Please refer to the additional remark below for more information about the error codes. 
6.  The operand n used in the 16-bit instruction should be in the range of 1 to 256, and the 
operand n used in the 32-bit instruction should be in the range of 1 to 128. 
7.  Only the 32-bit instructions can use the 32-bit counter. 
8.  Please refer to the regulation of the operands in the instruction TO for more information about 
the numbering of the special modules.