Chapter 5 Temperature Measurement Module AH04PT/AH08PTG 
5-53 
(3)  Please connect a shielded cable and a hermetically sealed cable with the ground 
separately. 
(4)  Terminals with insulation sleeves can not be arranged as a terminal block. It is 
recommended that the terminals be covered with insulation tubes. 
(5)  The diameters of the input/output cables used should be in the range of 30 AWG to 24 AWG 
(0.3 mm to 0.6 mm). The lengths of the plastic jackets removed should be in the range of 7 
mm to 8 mm. The specifications for the terminals on AH08PTG-5A and the wiring of the 
terminals are shown below. The temperature of the copper lead wires used should be 
60/75°C. 
   
 
  External wiring 
(1)  AH08PTG-5A 
Shielded cable 1*
471.5u
,
A
(Ni100Pt100, 
Resistor)/
204.8uA
(Pt1000)*3
ADC
AG
INA
O0+
I0+
 I 0-
 O 0-
 FG
CH1
0~3 00
Ni 100/Ni1000
Pt100/Pt1000
Ω
O1+
I1+
 I1 -
 O 1-
 FG
3-Wire
CH0
+
-
471.5u
,
A
(Ni100Pt100, 
Resistor)/
204.8uA
(Pt1000)*3
ADC
AG
INA
O2+
I2+
 I 2-
 O 2-
 FG
CH3
0~3 00
Ni 100/Ni1000
Pt100/Pt1000
Ω
O3+
I3+
 I3 -
 O 3-
 FG
3-Wire
CH2
4-Wire
Ni1 00/Ni1 000
Pt100/Pt1 000*2
+
-
0 ~300
Ni10 0/Ni10 00
P t10 0/Pt1 000
Ω
2-Wire
Shielded cable 1*
Shielded cable 1*
Shielded cable 1*
 
*1. The cables or the shielded twisted pair cables for Ni100/Ni1000/Pt100/Pt1000 temperature 
sensors are used, and should be kept separate from other power cables and cables which 
generate noise. Please use a three-wire temperature sensor. If users want to use a two-wire