Chapter 8 Serial Communication Module AH10/15SCM
8-21
The use of the parameters:
The module is placed on the main rack. Therefore, the rack code stored in D40 is 16#0001.
The module is inserted in the first slot. Therefore, the slot code stored in D41 is 16#0000.
The mode of the data exchange through COM1 is stored in CR#7. Therefore, the control
register number stored in D42 is 16#0007.
Owing to the fact that the mode of the data exchange through COM1 occupies one register,
the value in D2 is 1.
The data which is written into CR#7 is stored in D100. Therefore, the value in D100 is
16#0002.
The regulation of the operands in the instruction:
The operand m
1
specifies the rack code. It should be in the range of 1 to 8. 1 represents a
main rack, and 2~8 represent extension racks.
The operand m
2
specifies the slot code. It should be in the range of 0 to 11. If the rack code is
1, the slot code should be in the range of 0 to 11. If the rack code is in the range of 2 to 8, the
slot code should be in the range of 0 to 7.
The operand m
3
specifies the control register number. The 16-bit memories built in the special
modules are called the control registers. The control register numbers are decimal numbers
#0~#N, and the number of control registers varies with the module. The operating conditions of
the special module and the setting values are stored in the control registers.
At most 68 special modules can be placed on the rack, and they do not occupy inputs/outputs.
If the instruction FROM/TO is used, one control register is taken as a unit for the
reading/writing of the data. If the instruction DFROM/DTO is used, two control registers are
taken as a unit for the reading/writing of the data.
The n which is 2 in the 16-bit instruction has the same meaning as the n which is 1 in the 32-bit
instruction.
D0
D1
D2
D3
D4
D5
CR #5
CR #6
CR #7
CR #8
CR #9
CR #10
16 -bit instruction: n=6
Specified
device
Specified
control register
D0
D1
D2
D3
D4
D5
CR #5
CR #6
CR #7
CR #8
CR #9
CR #10
32-bit instruction: n=3
Specified
device
Specified
control register