AH500 Module Manual 
8-28 
 
 
The TCP keepalive period by default is set to 30 seconds. D500 is an initial register in which 
statuses of data exchanges are stored. Users can enter MODBUS Advance to alter the initial 
register.
 
 
 
  Triggering the reading/writing of data   
Users can use the instruction TO in ISPSoft to trigger the reading of data from bit devices/word 
devices, and the writing of data into bit devices/word devices. (CR#7, CR#8, CR#17, and 
CR#18) 
7  R/W 
Triggering the reading 
of data through COM1 
High byte: Reading data from bit devices 
Low byte: Reading data from word devices 
0: Not triggering it   
1: Triggering it once 
2: Always triggering it 
17  R/W 
Triggering the reading 
of data through COM2 
High byte: Reading data from bit devices 
Low byte: Reading data from word devices 
0: Not triggering it 
1: Triggering it once 
2: Always triggering it 
8  R/W 
Trigg
data through COM1 
High byte: Writing data into bit devices 
Low byte: Writing data into word devices 
0: Not triggering it 
1: Triggering it once 
2: Always triggering it 
18  R/W 
Triggering the writing of 
data through COM2 
High byte: Writing data into bit devices 
Low byte: Writing data into word devices 
0: Not triggering it 
1: Triggering it once 
2: Always triggering it 
 
If users want to continually trigger the reading of data from word devices, they can write 2 into 
CR#7. If users wan to trigger the reading of data from word devices once, they can write 1 into