Chapter 8 Serial Communication Module AH10/15SCM
8-35
the recording of all communication through COM1 and COM2 will stop. If Upload COM PORT
History Data is selected, all communication data in AH10/15SCM-5A will be uploaded to SCMSoft.
Please notice that the recording of all communication data stops before the data is uploaded to
SCMSoft. If users want resume the recording of communication data, they must enable the COM
port history function again.
8.7 Application
8.7.1 Modbus
This section introduces the how AH10/15SCM-5A is connected to other Delta industrial products
such as a human-machine interface, a temperature controller, a programmable logic controllers, an
AC motor drive, and a servo motor through Modbus. The connection framework is as follows.
Product
Slave
ID
Communication
protocol
Device from
which data
is read
Register
in the CPU
module
Device into
which data
is written
Register in
the CPU
module
HMI
5
9600, RTU, 8, E, 1
-
-
-
-
VFD 10 38400, ASCII, 7, E, 1 16#2103 D100
16#2000
16#2001
D150~
D151
ASDA 11 38400, ASCII, 7, E, 1
16#0101
16#020A
D200
D201
16#0101
16#020A
D250
D251
PLC 12 38400, ASCII, 7, E, 1
D100~
D109
D300~
D309
D200~
D204
D350~
D354
TC 13 38400, ASCII, 7, E, 1
16#1000
(Present
value)
D400
16#1001
(Setting
value)
D451