AH500 Module Manual 
10-26 
7.  The DeviceNet Builder software is called out, where select “Network” >> “Online”. 
 
 
8.  Select “Network” >> “Download” to download the starting address of the mapping area and the 
configuration data to AH10DNET-5A after the network enters the online mode and the 
configuration is completed. 
 
 
9.  Power off the AH500 series CPU module and then power it on again after downloading is 
finished. And at the time, the starting address of the mapping area is modified successfully. 
Method 2: Modifying the starting address of the mapping areas through DeviceNet Builder 
Note: Compared to the first method, the second one is a bit simpler but D device is probably used by 
multiple modules at the same time because of no uniform configuration through HWCONFIG. 
Please think carefully before adopting this method. 
1.  PC accesses an AH500 series CPU module via USB after connecting the device according to 
the following figure.