AH500 Module Manual
10-30
4. Select Network >> Scanner Setting and then the Scanner Settingdialog box pops up. By
picking Master Modeand Enable, the extension baud rate function is started up. Afterwards,
select an appropriate baud rate according to the actual demand. Click OKafter selection is
over.
Note: If “Slave Mode” is selected, AH10DNET-5A will be set to a slave eventually.
5. Select Network >> Downloadand then the following dialog box appears, where click OKto
download the configuration data to AH10DNET-5A automatically.
Note: If “E7” is displayed on AH10DNET-5A, please remove its DeviceNet terminals before
downloading. Otherwise, failure to download will occur.
6. After downloading is completed, turn both of the function switch DR0 and DR1 of
AH10DNET-5A to ON and then repower the AH500 series CPU module. At the time, the
extension baud rate setting is finished.