Chapter 10 DeviceNet Communication Module AH10DNET
10-45
The device connected to AHCPU530-EN will be scanned.
6. 10DNET in the window is the abbreviation of AH10DNET-5A. Double click the icon of 10DNET
and then the parameter setting window of 10DNET will pop up.
Set the mapping starting address of D in the INPUT area (the initial input mapping address) and
the OUTPUT area (The initial output mapping address). In this example, the two addresses are
set to D2000 and D2500 respectively. Click OKafter setting is over.
7. Select “Option>>Downloadto download the above setting to AHCPU530-EN.