Chapter 10 DeviceNet Communication Module AH10DNET 
10-63 
E8 
AH10DNET-5A is initializing. 
If initializing lasts too long, please repower 
AH10DNET-5A.
 
E9 
An error in the modules on the 
rack connected to 
AHRTU-DNET or the extension 
rack error 
1.  Check if the modules on the rack connected 
to AHRTU-DNET are normal. 
2.  Check if the extension rack connected to 
AHRTU-DNET is connected normally. 
10.10.3  Software Diagnosis 
When ISPSoft is used to read PLC system record, the following error codes may appear. 
16#A0F1 
No slave is configured in 
the scan list 
Configure the slave in the scan list and then download 
the scan list to AH10DNET-5A. 
16#A0F0 
The node address of 
AH10DNET-5A is 
repeated in that of other 
node or exceeds the valid 
range.
 
Ensure that the node address of AH10DNET-5A is 
unique and repower it after changing its node address. 
16#A0F2 
for AH10DNET-5A. 
Check if the work power for AH10DNET-5A and the 
AH500 series CPU module is normal. 
16#A0F3 
AH10DNET-5A enters the 
test mode.
 
Switch IN1 from ON to OFF and repower 
AH10DNET-5A.
 
16#A0F4 
AH10DNET-5A enters the 
bus-off state.
 
1. Check if the network cable is normal and the 
shielded wire has been grounded. 
2. Check if the baud rates of all node equipment on the 
network are the same.
 
3. Check if both ends of the network have been 
connected with a 121 Ω resistor respectively. 
4. Repower AH10DNET-5A.
 
16#A0F5 
DeviceNet network is 
detected.
 
Make sure that the cable is correctly connected and 
check if the network power supply is normal.
 
16#A0F6 
errors in AH10DNET-5A 
If the error still exists after power on again, send your 
AH10DNET-5A back to the factory for repair. 
16#A0F7 
Data exchange unit errors 
in AH10DNET-5A 
If the error still exists after power on again, send your 
AH10DNET-5A back to the factory for repair. 
16#A0F8 
detection errors in 
AH10DNET-5A
 
If the error still exists after power on again, send your 
AH10DNET-5A back to the factory for repair.
 
16#A0F9 
Errors in reading/writing 
the configuration data 
If the error still exists after power on again, send your 
AH10DNET-5A back to the factory for repair. 
16#A0FA 
The node address of 
AH10DNET-5A is 
repeated in that of the 
slave configured in the 
scan list.
 
Method 1: Reset the node address of AH10DNET-5A, 
which must be different from that of the slave 
configured in the scan list and then repower it.
 
Method 2: Do not configure any slave in the scan list. 
Download the empty configuration to AH10DNET-5A 
by using the “Simulate online” function. Finally, repower 
it.
 
16#A0FB 
between AH10DNET-5A 
and AHCPU fails. 
If the error still exists after AH CPU and AH10DNET-5A 
are repowered, send your AH10DNET-5A back to the 
factory for repair.   
16#A0FC 
Some error occurs in the 
slave or in the modules 
on the rack connected to 
AHRTU-DNET or the 
1.  Check if the node address of the slave has been 
changed. 
2.  Check if the network cable is connected normally in 
case it is loose or cut.