AH500 Module Manual
11-48
Command Edit interface:
Explanation of Command Edit interface:
Item
Explanation
Command No.
Each group has its number and the execution order is specified
through the number.
Command Type
Send, Receive and Send & Receive are for option.
Send Packet
The name of the packet already built in the group could be selected.
Receive packet
The name of the packet already built in the group could be selected.
Success
It specifies the action after the command execution is completed. Next,
Goto and End are for option.
Next: To execute the next command
E.g. the number of the currently executed command is 1; the next
one to be executed is the command of number 2.
Goto: To skip to execute the command
Directly specifies the command of a bigger number.
End: Finish
Fail
To specify the action after the command execution is completed; Next,
Goto and End are for option.
Next: To execute the next command. E.g. the number of the currently
executed command is 1; the next one to be executed is the
command of number 2.
Goto: To skip to execute the command; directly specify the command
of a bigger number.
End: Finish.
Retry
The retry times when transfer failure occurs
Repeat
The repeated execution times when the command execution succeeds
Transfer delay
The interval time for sending every message; default: 0 which means
that the next command will be sent out immediately once the response
is received
Timeout
After the serial port releases the command, no response is received
within the set time, that is, communication timeout. Default: 50 ms