AH500 Module Manual 
11-104 
11.7.1  Indicator Diagnosis 
  NS indicator 
Off  No power or bus OFF 
1.  Make sure that AHRTU-DNET-5A is powered 
and is connected normally. 
2.  Check if the communication is normal and the 
baud rate of AHRTU-DNET-5A is the same as 
that of the master. 
Green light 
blinking 
between 
AHRTU-DNET-5A and 
the DeviceNet master 
Configure AHRTU-DNET-5A in the DeviceNet 
software properly and download the configuration 
Green light 
ON 
between 
AHRTU-DNET-5A and 
the DeviceNet master 
is normal. 
-- 
Red light 
blinking 
when there is an I/O 
connection between 
AHRTU-DNET-5A and 
the DeviceNet master. 
Refer to the error codes on the digital displayer to 
shoot the trouble. 
Red light ON 
Network error, ID 
duplication, no 
network power, or 
bus-off   
1.  Make sure all the devices have their unique 
node address. 
2.  Check if the network installation is correct 
3.  Check the baud rate of AHRTU-DNET-5A is 
the same as that of the bus. 
4.  Check if the node address of 
AHRTU-DNET-5A is valid. 
5.  Check if the network power is normal. 
 
  MS indicator 
Off  No power   
Make sure that AHRTU-DNET-5A is 
powered and is connected normally. 
Green light 
blinking 
waiting for the I/O data of 
the DeviceNet master 
2.  No I/O data between 
AHRTU-DNET-5A and the 
DeviceNet master 
3.  PLC connected to the 
master is in STOP state 
1.  Configure AHRTU-DNET-5A in the 
DeviceNet software properly and 
download the configuration. 
2.  Switch PLC to RUN state. 
ON 
I/O data transmission is normal  -- 
Red light 
blinking 
No network power, configuration 
problem or module warning 
1.  Check if the network power is 
normal. 
2.  Reset the internal parameters in 
AHRTU-DNET-5A. 
3.  Check if there is any error or warning 
in some module.