Chapter 13 PROFIBUS Slave Module AH10PFBS
13-13
The high byte of the state register is used for monitoring whether the CPU module is in RUN or
STOP state and the low byte is for monitoring whether the work state of AH10PFBS-5A is normal.
See the indication of the state register values in the following table.
Byte
Content
value
Indication How to correct
High byte
0
The CPU module is in RUN state.
--
80 The CPU module is in STOP state
Turn the RUN/STOP switch of the
CPU module to RUN.
Low byte
0
AH10PFBS-5A is in normal state.
--
F0~F6
AH10PFBS-5A can not work
normally.
See digital displayer in Section 8.2
on how to deal with problems
indicated by F0~F6.
13.8.4 Diagnosis via ISPSoft
While ISPSoft is being used to read the system log of PLC, the meanings of error codes occurring
in the PROFIBUS network are shown below.
When ISPSoft is in state of monitoring, please select menu “PLC”>System Log” option to find the
system log as below.