Chapter 14 Remote I/O Communication Module AHRTU-PFBS
14-3
14.2.2 Specification
PROFIBUS DP port
Interface DB9 connector
method
High-speed RS-485
Two-wire twisted shielded cable
Electrical isolation 500 VDC
Communication
Message type Cyclical data exchange
Module name AHRTU-PFBS -5A
GSD file DETA09B9.GSD
Product ID 09B9
Serial
transmission
speed supported
(auto-detection)
9.6kbps; 19.2kbps; 45.45kbps;93.75kbps; 187.5kbps; 500kbps;
1.5Mbps; 3Mbps; 6Mbps; 12Mbps
Electrical Specification
Power supply
voltage
5VDC
Insulation voltage 500VDC
Power
consumption
2W
Weight 200g
Environment
Noise immunity
RS (IEC 61131-2, IEC 61000-4-3): 80~1, 000 MHz, 1.4 ~ 2 GHz, 10 V/m
EFT(IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1 kV
ESD(IEC 61131-2, IEC 61000-4-2): 8 kV Air Discharge
Storage/operation
:
-25 ~ 70°C(temperature), 5 ~ 95% (humidity)
Operation:0 ~ 55°C(temperature), 5~ 95% (humidity), pollution level 2
Shock/vibration
immunity
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC
61131-2 & IEC 68-2-27(TEST Ea)