Chapter 14 Remote  I/O Communication Module  AHRTU-PFBS 
14-11 
Special module 
model 
Mapping parameter (length) 
parameters in each channel 
(Length) 
AH04AD-5A 
Digital value converted from the 
analog quantity of input 
CH0~CH3 of AH04AD(Length=8) 
Digital value in Byte0~ Byte1 
that the input channel 0 
corresponds to(Length=2) 
Digital value in Byte2~ Byte3 
that the input channel 1 
corresponds to(Length=2) 
Digital value in Byte4~ Byte5 
that the input channel 2 
corresponds to(Length=2) 
Digital value in Byte6~ Byte7 
that the input channel 3 
corresponds to(Length=2) 
 
2.  Conversion between analog modules and digital modules that AHRTU-PFBS supports: 
When the input / output mode of the analog module is positive voltage or positive current, 
the corresponding digital value is 0 ~32000; for example, if the modes are 0V~10V and 
4mA~20mA, the corresponding digital values are both 0~32000. 
 
When the input /output mode of the analog module is negative voltage or negative 
current, the corresponding digital value is -32000~32000; for example, the modes are 
-10V~+10V, and -20mA~20mA, the corresponding digital values are both -32000~32000. 
 
3.  AHRTU-PFBS-5A must be installed to the CPU slot of the main rack; supports maximum 
8 racks including 1 main rack and maximum 7 extension racks and 48 I/O modules.