AH500 Module Manual 
14-24 
 
When some I/O module has a fault and the master is disconnected or stops, the DO and AO 
modules added to AHRTU-PFBS-5A are set as the above two figures shows. Besides, anyone 
of them can also be set separately. Take a DO module for example as below. 
 
 
 
Name  Setting  Explanation 
rack  0x01 
The number of the rack where the I/O module is 
(Rack number ranges from 1 to 8, 1 represents 
the main rack, 2~8 stand for extension racks and 
the slot number is 0~11.)   
slot  0x00 
The number of the slot on the rack where the I/O 
module is. (Rack number ranges from 1 to 8, 1 
represents the main rack, 2~8 stand for 
extension racks and the slot number is 0~11). 
Output hold  disable/enable 
 
Enable: the output of other I/O modules of 
AHRTU-PFBS-5A is held when some I/O 
module has a fault and the master is 
disconnected or stops running. 
 
Disable: the output of other I/O modules of 
AHRTU-PFBS-5A is cleared to 0 when some I/O 
module has a fault and the master is 
disconnected or stops running.