Settings of the digital modules and special modules connectable to AHRTU-PFBS-5A are
introduced below.
Settings of all digital modules are same and the following will make the introduction of the
setting by taking AH16AP11R-5A as an example.
Setting of AH16AP11R-5A
After configuring AH16AP11R-5A, refer to Figure 0 for the related parameters setting.
Figure 0
Explanation of the options above
Name Setting Explanation
rack 0x01
The number of the rack where the I/O module is
(Rack number ranges from 1 to 8, 1 represents the
main rack, 2~8 stand for extension racks and the
slot number is 0~11.)
slot 0x00
The number of the slot on the rack where the I/O
module is. (Rack number ranges from 1 to 8, 1
represents the main rack, 2~8 stand for extension
racks and the slot number is 0~11).
Output hold disable/enable
Enable: the output of other I/O modules of
AHRTU-PFBS-5A is held when some I/O module
has a fault and the master is disconnected or stops
running.
Disable: the output of other I/O module
AHRTU-PFBS-5A is cleared to 0 when
some I/O module has a fault and the
master is disconnected or stops running.