Chapter 14 Remote I/O Communication Module AHRTU-PFBS
14-65
Explanation of the options above
Name Setting Explanation
rack 0x01
The number of the rack where the I/O module are
placed (Rack number is 1~8, 1 represents the main
rack, 2~8 are extension racks and the slot number
is 0~11.)
slot 0x00
The number of the slot on the rack where the I/O
module is. (Rack number is 1~8, 1 represents the
main rack, 2~8 are extension racks and the slot
number is 0~11).
Output hold disable/enable
Enable: the output of other I/O modules of
AHRTU-PFBS-5A is held when some I/O module
has a fault and the master is disconnected or stops
running.
Disable: the output of other I/O modules of
AHRTU-PFBS-5A is cleared to 0 when some I/O
module has a fault and the master is disconnected
or stops running.
Pick “AH06XA-5A” and the related parameters are displayed as follows. The input modes of
CH0~CH3 are all set to -10V~+10V。