Chapter 16 Remote I/O Module  AHRTU-ETHN-5A 
16-5 
5  X1 Ack indicator  6  X2 Link indicator 
7  X2 Ack indicator  8  X1/X2 of RJ-45 port 
9  MS indicator  10  NS indicator 
11  I/O indicator     
 
16.2.3  Ethernet Connector 
The pins of Ethernet connector are defined in the following table.   
Pin No.  Name  Description  RJ-45 figure 
1  TX+  Positive pole for transmitting data   
 
2  TX-  Negative pole for transmitting data   
3  RX+  Positive pole for receiving data   
4  -  - 
5  -  - 
6  RX-  Negative pole for receiving data   
7  -  - 
8  -  - 
 
16.2.4  IP Address Switch 
The rotary switch of AHRTUETHN can be used for setting its IP address. The default domain is 
192.168.1.x and the range of X is 00~FF. 
value 
Description 
 
 
00 ~ 16#FD 
1.  Valid IP address: 192.168.1.x, x = 1 ~ FD, 
(1~253) 
2.  16#00: Set through the EIP Builder software. 
16#FE 
Firmware update mode: The IP address will 
become 192.168.1.3 after connecting 
AHRTU-ETHN-5A to the network, switching the 
rotary switch to FE and repowering the module.   
For details, refer to Firmware update page of 
Network configuration in section 16.5.3.4. 
16#FF 
The module will be restored to the factory settings 
and the settings are not valid until the module is 
restarted. 
 
16.3  Installation of AHRTU-ETHN-5A 
16.3.1  Installed to Backplanes 
AHRTU-ETHN-5A can only be inserted to the CPU slot of AH series main backplane. For details on 
the installation, see the instructions below. 
Insert the projection at the bottom of the module to the hole of the backplane and push the module 
in the direction indicated by the following arrow to meet the CPU port of the backplane.