Chapter 16 Remote I/O Module AHRTU-ETHN-5A
16-11
Number Attribute
Name Description
0: No module exists. 1: The module exists.
b4
0: Inconsistent with the software configuration.
1: consistent with the software configuration.
SR21~28: The states of I/O modules 0~7 on the
extension backplane 1
SR29~36: The states of I/O modules 0~7 on the
extension backplane 2.
And so on…
77 R RTU error code Refer to Troubleshooting in section 16.7.
78-89 R
modules on RTU’s
main backplane
Display the error codes of I/O modules 0~11 on the
main backplane. For details, refer to the explanation of
error codes in modules.
90-145 R
Error codes of I/O
modules on RTU’s
extension backplanes
1~7
Display the error codes of I/O modules 0~7 on the
extension backplane 1~7.
SR90~97: The error codes of I/O modules 0~7 on the
extension backplane 1
SR98~105: The error codes of I/O modules 0~7 on the
extension backplane 2.
And so on…
For details, refer to the explanation of error codes in
modules.
16.4.3 RTU Input Register
Number Attribute
Name Description
0 R Status
0: Normal, 1: Alarming, 2: In error, 3: A fault exists but the
module does not stop working.
1 R Reserved
2 R Error code Error code in AHRTU
3~10 R Reserved
11~15 R I/O module status
The status of every I/O module is expressed with one bit.
(0: normal operation; 1: abnormal)
Bit0 of number 11 stands for I/O module 0 on the main
backplane.
Bit 1 of number 11 is I/O module 1 on the main
backplane and Bit
11 of number 11 is I/O module 11 on the
main backplane. Bit 12 of number 11 indicates I/O module
0 on the extension module and so on.